EVS800-1600 Series Low Voltage Vacuum Contactor Vacuum Switch Small Size

Place of Origin China
Brand Name GUOGUANG
Model Number EVS800-1600
Minimum Order Quantity 1
Price USD214-900Piece/Pieces
Packaging Details export packing
Delivery Time 5-8Work day
Payment Terms T/T
Supply Ability 500 Set/Sets per Month

Contact me for free samples and coupons.

Whatsapp:0086 18588475571

Wechat: 0086 18588475571

Skype: sales10@aixton.com

If you have any concern, we provide 24-hour online help.

x
Product Details
Rated Voltage 1140V Rated Current 800A,100A,1250A,1600A
Name Low Voltage Vacuum Contactor Origin China
High Light

high voltage vacuum contactor

,

low voltage vacuum contactor

Leave a Message
Product Description

EVS800-1600 Series Low-voltage Vacuum Contactor

EVS(800-1600)/1140 series low-voltage vacuum contactor is a single pole structural unit, it can assemble to n poles according to customer’s requirement. Its operating mechanism is electromagnetic holding,DC magnetic system. When using AC control power source, it supply DC to coil through rectifier. Under AC-1, AC-2 class of application, it is suitable for the occasions requiring high-current control.

 

Main circuit rated voltage (V) 1140V
Main circuit rated current (A) 800A, 1000A, 1250A, 1600A
Main circuit making capacity (A) 4Ie (AC-2)
Main circuit breaking capacity (A) 4Ie (AC-2)
Main circuit rated frequency (Hz) 50/60 Hz
Mechanical life (time) 100 x 104
Electric life AC-2 (time) 25 x 104
Rated operating frequency (time/h) 300
Main circuit power frequency withstand voltage (gap) (kV) 10 kV
Phase to Phase, Phase to earth power frequency withstand voltage (kV) 5 kV
Main circuit contact resistance (μΩ) ≤100 μΩ
Clearance between open contacts (mm) 2.5±0.5 mm
Overtravel (mm) 2.5±0.5 mm
Secondary contdrol voltage (V) AC:110 /220/380V, DC:110/220V
Making time (ms) ≤50 ms
Breaking time (ms) ≤50 ms
Making bounce (ms) ≤3 ms